Piston Flow Switches

FBC230

Piston Flow Switch

Inline mechanical piston flow switch for low-flow liquid monitoring.

CASCED FBC230 piston flow switch
RANGE0.03–1.2 L/min
OUTPUTReed switch, 24 VDC/250 VAC, 100 mA
MATERIALNickel-plated brass housing (T ordering code); brass piston; stainless-steel spring
PROTECTIONIP65

Product overview

Application-focused measurement and switching.

Inline mechanical piston flow switch for low-flow liquid monitoring.

Configuration note

Ratings, materials, interfaces, and approvals can vary by ordered configuration. CASCED INC confirms the controlled specification before order acceptance.

Key features

  • Setpoint scale
  • LED status on DC versions
  • One or two switch points
  • Plastic, anodized-aluminum, or stainless-steel housing options

Technical specifications

Key data for product selection.

Technical setpoint range
0.03–1.2 L/min
Ordering-code range
012 = 0.03~1.2 L/min
Accuracy
±5% FS
Output
Reed switch, 24 VDC/250 VAC, 100 mA
Pressure
Catalog body-dependent ratings: plastic 10 bar; aluminum 50 bar; stainless steel 100 bar. The T nickel-plated-brass configuration rating requires confirmation.
Maximum media temperature
100°C
Protection
IP65
Calibration medium
No. 46 lubricating oil at 20°C, horizontal installation
Material
Nickel-plated brass housing (T ordering code); brass piston; stainless-steel spring

Further dimensions, connection diagrams and ordering details are in the current catalog, full pages 184–185. Open the matching English PDF pages. Published values and options are configuration dependent. Confirm the selected configuration before use.

Downloads

Technical documentation

View in your browser or download a copy for engineering and sourcing review.

Typical applications

Engineered for real industrial systems.

01Central lubrication
02Industrial automation
03Machinery
04Compressed air
05Refrigeration and air conditioning

Contact technical sales

Share your operating conditions, interfaces, quantity, and documentation requirements.

Every website inquiry is submitted securely to info@casced-us.com.

Close help

How can we help?

Answers to common questions. For application-specific advice, contact our team.

How can I find a product?

Browse by product group or category, or search by model, specification, or application in our Product Center.

Browse products
Where can I find a datasheet?

Search by model, product name, or category. English PDFs are review references; final ratings and options require confirmation for the ordered configuration.

Find datasheets
Can you review a custom sensor configuration?

Send your operating conditions, mechanical and electrical requirements, expected quantity, and timeline for case-by-case review.

Request a review
Can you help with an older wind turbine sensor?

Submit the existing part number, application details, and any photos or drawings. A candidate configuration requires engineering review.

Submit a custom sensor request
How do I speak with your team?

Send a general question through our contact form or email info@casced-us.com. A team member will follow up.

Contact our team
Can I order one unit, and how are warranty and delivery confirmed?

Single-unit orders are accepted. Warranty is one year. Lead time is no longer than four weeks from receipt of the agreed deposit; the written quotation or order confirms the configuration, price, warranty handling and delivery schedule.

Ask about a unit or sample
Ask our team a question

This is an instant FAQ, not a live chat or engineering approval.